TRANSFORMER CHARACTRISTICS:
• Units are resistant to short-circuit forces.
• Transformer has low losses and low sound level.
• Units are non-polluting and require little maintenance.
• Transformers are free of partial discharge and withstand high Basic Impulse Levels.
TECHNICAL DATASHEET
Model | Io(%) | LPA(dB) | Uk(%) | P0 [W] | Pk at 120°C[W] |
SCB-800/35 | 1.3 | 57 | 6 | 2250 | 9400 |
SCB-1000/35 | 1.3 | 57 | 6 | 2670 | 10900 |
SCB-1250/35 | 1.1 | 59 | 6 | 3130 | 12900 |
SCB-1600/35 | 0.9 | 60 | 7 | 3690 | 15400 |
SCB-2000/35 | 0.9 | 60 | 7 | 4230 | 18200 |
SCB-2500/35 | 0.7 | 62 | 8 | 4860 | 21800 |
SCB-3150/35 | 0.7 | 62 | 8 | 6030 | 24500 |
SCB-4000/35 | 0.5 | 64 | 8 | 7020 | 29400 |
SCB-5000/35 | 0.5 | 64 | 8 | 8370 | 34900 |
SCB-6300/35 | 0.4 | 65 | 9 | 9900 | 40800 |
SCB-8000/35 | 0.4 | 65 | 9 | 11300 | 46000 |
SCB-10000/35 | 0.4 | 67 | 9 | 12900 | 55500 |
SCB-12500/35 | 0.4 | 67 | 9 | 15700 | 64600 |
SCB-16000/35 | 0.3 | 67 | 9 | 19300 | 76000 |
SCB-20000/35 | 0.3 | 70 | 10 | 22900 | 85500 |
SCB-25000/35 | 0.3 | 73 | 10 | 27100 | 101000 |
CAST RESIN DRY TYPE TRANSFORMER FOR OTHER APPLICATIONS
• OLTC DRY TYPE TRANSFORMER
When the voltage of the power network fluctuates, transformer vo Itage must be adjusted to supply stable electricity of high quality. Equipped with an automatic controller, the on-load ta p changer can be controlled on-site or from remote computer. If necessary, we would equip and design high quality and d reliable OLTC switch.
• TRANSFORMER FOR NUCLEARL POWER PLANT
Rated power: 500~1250kVA
Voltage class: 10KV.
lt is applied d to 1E electrical system of nuclear reactor and nuclear power plant.
• RECTIFICATION TRACTION TRANSFORMER
Rated power: 800~4400Kva
Voltage class: 10kV, 35KV
12-pules and 24-pules rectification, apply to power supplying system of metro subway and rail transportation. The e harmonic wave pollution of 24-pulse rectification circuit is 50% less than that of 12-pulse rectification circuit.
• TRANSFORMER FOR ELECTRIFIED RAILWAY STATION
Rated power: 20~315KVA,
Voltage class: 27.5kV
Vector group: Dyn11, li0, llyn0 (two phases-three phases).
The transformer is applicable to station power system of electrical railway traction substation, switching station, AT station and breaking station.
• RECTIFICATION EXCITATION TRANSFORMER
Rated power: 315~3000kVA,
Voltage class: 10kV、13.8kV、15.75kV、20kV、22kV.
Single phase structure, separated HV incoming enclosed busbar, shield equipped between HV winding and LV winding. The transformer is applicable to static excitation system of hydropower plant and thermal power plant.
• NORMAL RECTIFICATION TRANSFORMER
Rated power: 315~4000kVA,
Voltage class: 10kV, 35KV.
This transformer is applicable to rectification system of industrial and mining industrial establishment.
• THREE-PHASE FIVE-CORE LEGS RECTIFICATION TRANSFORMER
Rated power: 30~2500kVA,
Voltage class: 10kV, 35kV.
This transformer is used in the double reversed star rectification circuit to cancel the balance reactor and reduce the impact of the voltage regulating current and the transit height. It is applicable in the room-limited transformer or the reversed rectification system.
• TRANSFORMER FOR ELECTRIC METALLURGIC FURNACE
Rated current: less than 20000A
Voltage classes: 10KV, 35KV
Equipped with no-load tap changer. The transformer is applicable to power system of electrical metallurgic furnace with large current.
• MARINE(OFFSHORE) OIL PLATFORM TRANSFORMER
Rated power: 30~10000kVA,
Voltage class: 0.38~35kV.
The transformer is applicable to the power system of vessel and offshore oil platform.
• AUTO-TRANSFORMER
Rated power: 30~2500kVA
Voltage class: 10kV, 35kV.
The transformer is applicable to initiating system of motor and can reduce the cost.
Dry type transformers for other special applications are not listed in details. Please feel free to contact us if you need other dry type transformer for special applications.