Availability: | |
---|---|
Quantity: | |
ADVANTAGES
• Efficient & Quiet
• Environmentally Safe
• Dielectric Integrity
• Low Installation Cost
TECHNICAL DATASHEET
Model | H.V(kV) | L.V(KV) | Uk(%) | P0 [W] | Pk at 120°C[W] |
SCB-50/35/0.4 | 35 | 0.4 | 6 | 450 | 1420 |
SCB-100/35/0.4 | 35 | 0.4 | 6 | 630 | 2090 |
SCB-160/35/0.4 | 35 | 0.4 | 6 | 790 | 2710 |
SCB-200/35/0.4 | 35 | 0.4 | 6 | 880 | 3320 |
SCB-250/35/0.4 | 35 | 0.4 | 6 | 990 | 3800 |
SCB-315/35/0.4 | 35 | 0.4 | 6 | 1170 | 4510 |
SCB-400/35/0.4 | 35 | 0.4 | 6 | 1370 | 5410 |
SCB-500/35/0.4 | 35 | 0.4 | 6 | 1620 | 6650 |
SCB-630/35/0.4 | 35 | 0.4 | 6 | 1860 | 7690 |
SCB-800/35/0.4 | 35 | 0.4 | 6 | 2160 | 9120 |
SCB-1000/35/0.4 | 35 | 0.4 | 6 | 2430 | 10400 |
SCB-1250/35/0.4 | 35 | 0.4 | 6 | 2830 | 12700 |
SCB-1600/35/0.4 | 35 | 0.4 | 6 | 3240 | 15400 |
SCB-2000/35/0.4 | 35 | 0.4 | 6 | 3820 | 18200 |
SCB-2500/35/0.4 | 35 | 0.4 | 6 | 4450 | 21800 |
• TEMPERATURE CONTROLLING SYSTEM
The steady running and longevity of service of the transformer rely on the reliability and safety of the transformer winding. And the insulation damage of the transformer winding by heating o over the insulation tolerance temperature is one of the main causes of the transformer damage. The new type of multifunctional computer temperature controlling system designed for air-cooled dry-transformer. The temperature of winding gs can be detected by Pt100 heat-sensitive resistance embedded in the windings, and be displayed on the board. And the system can send automatically the corresponding signals of starting and stopping, alarm and brake by referring the data of the detecting temperature and the pre-setting control temperature to ensure the safe operation of the transformer.
• FUNCTIONS OF TEMPERATURE CONTROLLER
• Inspection and display of three-phase winding temperature
• Manual or automatic start/stop of fans
• Over-temperature alarm, over-temperature tripping contacts output.
• Fault self-test function
• Output in RS485 computer interface
• Analog temperature output: 4~20mA.
PROJECT REFERENCE
SHEEPMOOR Traction substation for Trans Net
VRYHEID EAST Traction substation for Trans Net
DUMBE Traction substation for Trans Net
RANDFONTEIN Local Municipality Project in SA
Transformer to CINERWA Cement Plant Project in Rwanda
Transformer to Hydropower project in Vietnam
Locomotive Transformer Project for Toshiba
Transformer to Project for GBE in Italy
Transformer to AEON NILAI MALL Project in Malaysia
Transformer to COUNTRY GARDEN FOREST CITY Project in Malaysia
TNB COMPACT SUBSTATION TRANSFORMER Project in Malaysia
Transformer to CONFERNCE CENTER Project in Malaysia
Transformer to Australian Perth Solar Power Plant
Transformer to 133MW gas natural gas fired power plants in Myingyan, Myanmar