Availability: | |
---|---|
Quantity: | |
MAIN FEATURES
• Non-Flammable and self-extinguishing.
• Non-polluting and require little maintenance.
• High Short-Circuit Strength
• Designs are compact and light weight
TECHNICAL DATASHEET
Model | H.V(kV) | L.V(KV) | Uk(%) | P0 [W] | Pk at 120°C[W] |
SCB-50/20/0.4 | 20 | 0.4 | 6 | 340 | 1230 |
SCB-100/20/0.4 | 20 | 0.4 | 6 | 540 | 1990 |
SCB-160/20/0.4 | 20 | 0.4 | 6 | 670 | 2470 |
SCB-200/20/0.4 | 20 | 0.4 | 6 | 730 | 2940 |
SCB-250/20/0.4 | 20 | 0.4 | 6 | 840 | 3420 |
SCB-315/20/0.4 | 20 | 0.4 | 6 | 970 | 4080 |
SCB-400/20/0.4 | 20 | 0.4 | 6 | 1150 | 4840 |
SCB-500/20/0.4 | 20 | 0.4 | 6 | 1350 | 5790 |
SCB-630/20/0.4 | 20 | 0.4 | 6 | 1530 | 6840 |
SCB-800/20/0.4 | 20 | 0.4 | 6 | 1750 | 8260 |
SCB-1000/20/0.4 | 20 | 0.4 | 6 | 2070 | 9780 |
SCB-1250/20/0.4 | 20 | 0.4 | 6 | 2380 | 11500 |
SCB-1600/20/0.4 | 20 | 0.4 | 6 | 2760 | 13800 |
SCB-2000/20/0.4 | 20 | 0.4 | 6 | 3420 | 16300 |
SCB-2500/20/0.4 | 20 | 0.4 | 6 | 3870 | 19300 |
MANUFACTURING CHARACTRISTICS:
Pearl Electric is recognized for its high-quality production.
Using state of the art constructional techniques and imported equipment, constant attention throughout the production process (ISO 9001:2015) and rigorous checks in the final phase, Pearl Electric guarantees quality for 100% of the production.
• HV WINDINGS
Made of high quality copper wire(available in aluminum) and cast in resin under vacuum.
• MAGNETIC CORE
Core in three columns made of magnetic steel laminations with high-permeability oriented crystals, available with different level of losses.
• LV WINDINGS
Made of high quality copper strip foil (available in aluminum) impregnated in resin under vacuum.
• OTHER COMPONENTS
• LV connections upwards (standard) or downwards version (on request)
• HV connections upwards (standard) or downwards version (on request).
• Rubber inserts attenuate the transmission of vibrations between core and windings and reduce to a minimum the operating noise generated by the transformer as well as absorbing the thermal expansion of the components.
• Off-load tapping links on the HV side to adapt the primary voltage to the mains, which can be set with transformer switched OFF.
• Structure, armatures and carriage, made in strong painted sheet steel (available on request hot – dip galvanized )
• Carriage with bi-directional rollers. The carriage allows safe movement and is pre-equipped for the mounting of an IP reinforced boxes.
• Lifting eyebolts conform to the IEC standards with safety hooking at 4 points.
• LV terminals with optional pre-equipment for connection of the LV - Zucchini busbar trunking system.
• Cooling fans could be optional. Under air forced coolig conditions, the transformer ouput capacity could be increased by 40~50%.